Answer: Officially, the pluggable installation is not covered by the European CPR legislation and no DoP may be issued for the pluggable installation.
But Dutch building legislation does set requirements for electrical cables in buildings. Until 31 December 2023, it was the Building Decree, and from 01 January 2024 it is the Environment Buildings Decree, the BBL.
The BBL requires that certain fire classes and smoke classes according to the Euro classes from the CPR be used for all electrical cables in buildings, and thus also pluggable installations. So in fixed installations, you are still required to use Dca s2 or B2ca s1 cabling, for example, for pluggable installations. So how does that work, exactly?
A pluggable electrical installation is a fixed installation with flexible cables that is used in buildings. Is a pluggable electrical installation covered by CPR? With pluggable electrical installations, we use a cable that meets the EN50575 standard and must therefore have a Euro class label. However, the manufacturer of pluggable electrical installations turns this into a new product, a pluggable electrical installation cable, which must comply with and be certified in accordance with the EN61535 standard. The manufacturer of pluggable electrical installations tests and certifies the new product as per EN61535, and issues a CE declaration as per EN61535. The product has changed and is now subject to EN61535, rather than EN50575. And this EN61535 standard is not assigned to the CPR. A pluggable electrical installation is not covered by the CPR. Please refer to this website: https://ec.europa.eu/growth/single-market/european-standards/harmonised-standards/construction-products_en
What about the Declaration of Performance (DoP)? A DoP is a certificate proving the Euro class of a building component as per the CPR. However, a pluggable electrical installation is not covered by CPR. Therefore, no DoP should be issued for it. This is only allowed on products covered by the standards assigned to the CPR. Wieland, manufacturer of pluggable installations, solves this by also indicating on the CE declaration they issue for their products which fire class the cables they use comply with. Of course, this will also be stated on the cable. If necessary, the DoP of the cable used in the product can also be issued.
According to Section 4.2.7, Art. 4.45a, the BBL requires that electrical cables comply with the fire classes and smoke class specified in Table 4.42. This also applies to electrical cables in a pluggable electrical installation. For both new construction and rebuilding, see Section 5.3 Art. 5.12.
Does the CPR apply to pluggable electrical installations; and the Building Decree? And what about the DoP, Declaration of Performance?
- › Does the CPR apply to pluggable electrical installations; and the Building Decree? And what about the DoP, Declaration of Performance?
- What is the CPR?
- Are GST18 cables in furniture also covered by CPR and NEN1010?
- What is the fire classification of old GST18 cables from before CPR legislation?
- What is the fire class or Euro class?
- What are the requirements of the Environment Buildings Decree (BBL) for cables per use function?
- Are separate GST and BST connectors also covered by CPR?
- Do cables in walls and ceilings also have to comply with the fire and smoke classes of the Environment Buildings Decree (BBL)?
- Do connecting conduits to appliances have to meet the fire class requirements set in CPR or Environment Buildings Decree (BBL)?
- What is the difference between smoke classes s1, s1a and s1b?
- Are separate GST and BST connectors also covered by CPR?
- May Eca cables still be used?