May Eca cables still be used?
‹ Terug naar overzicht- May Eca cables still be used?
Answer: The building code has been amended as of 1 June 2020. For new installations, the use of Eca cables in contact with indoor or outdoor air is no longer permitted. Eca cables are allowed only where they do not come into contact with the inside or outside air, for example cast in a concrete wall.
Open Contact opnemen - locatie_EN
- › May Eca cables still be used?
- What is the CPR?
- What is the fire class or Euro class?
- Does the CPR apply to pluggable electrical installations; and the Building Decree? And what about the DoP, Declaration of Performance?
- What requirements does the Building Decree set out for cables for each application?
- Do pluggable electrical installations comply with the fire class requirements of the CPR and the Building Decree?
- Are separate GST and BST connectors also covered by CPR?
- What is the difference between smoke classes s1, s1a and s1b?
- Do connecting cables to devices have to meet the fire class requirements of the CPR or the Building Decree?
- Are separate GST and BST connectors also covered by CPR?
- Are GST18 cables in furniture also covered by CPR and NEN1010?
- What is the fire classification of old GST18 cables from before CPR legislation?